STABITERM 222 is a single-component, water-based thick-film fire-retardant compound for structural fire protection of steel structures in industrial and civil construction. Fire protection — up to R150.
Where to use it
- indoors;
- outdoors under a canopy;
- on structures with high fire-resistance requirements — up to R150;
- where the coating has to withstand mechanical impact.
How it works
The compound forms a thick white heat-insulating layer that slows down heating of the steel in a fire. This is structural fire protection: the protective thickness is built up at application, not only during a fire.
222 vs thin-film paints
Thin-film intumescent paints such as STABITERM 217 provide up to 120 minutes and look like an ordinary paint coating. Thick-film STABITERM 222 is chosen when the design requires higher fire-resistance ratings — up to R150 — and a durable, impact-resistant coating. If you need a cement-based compound, see the STABITERM 002 and STABITERM 003 plasters.
Surface preparation and application
- The steel is cleaned of rust, mill scale, oil and dust and primed according to the fire protection design.
- The water-based compound is applied at no less than +5 °C to a dry primed surface.
- Coating thickness is checked against the fire protection design.
Consumption and coating thickness
We calculate consumption and fire-protective layer thickness for your project: they depend on the required fire-resistance rating and the section factor of each steel profile. Send us the steel specification and we will calculate it for every profile.
Specifications
| Base | water-based, single-component thick-film compound |
| Coating colour | white |
| Fire protection | up to R150 |
| Minimum application temperature | +5 °C |
| Where to use | indoors and outdoors under a canopy |
| Guaranteed service life | up to 25 years indoors |
Documents
The compound has Uzbek documents: a fire safety certificate of the Ministry of Emergency Situations of the Republic of Uzbekistan, a certificate of conformity and a quality passport for each batch. Available on request.
FAQ
Can 222 be used outdoors? Under a canopy — yes. For structures fully exposed to the weather we will select another product, such as the weather-resistant STABITERM 219 or STABITERM 209.
Why choose a thick-film compound over paint? It covers higher fire-resistance ratings — up to R150 — and gives a durable coating that resists mechanical impact.
How much compound does a project need? It depends on the required fire-resistance rating and the steel profiles. Send us the specification and we will calculate it.